GFS Power

Celltron Advanced

Celltron Advanced

The CELLTRON ADVANCED  is a professional level portable battery analyzer used for stationary battery management. Research proven technology and field-tested design make it a must for critical power maintenance in mobile telecom switching offices, cellular/wireless base stations, and telecom network outside plant installations. With the growing criticality of broadband systems for data and voice transmission, a testing program utilizing the CELLTRON ADVANCED increases maintenance efficiency and maximizes battery asset utilization all while ensuring power system reliability. Compatible with the PowerSure database, the CELLTRON ADVANCED measures individual cell and overall string health and voltage. Conductance technology allows for quick, simple, safe and accurate testing. Passive test method minimizes technician and system risk while reducing testing time to less than 10 seconds per cell. The CELLTRON ADVANCED provides consistent and repeatable on-line testing without battery discharge and tests both battery cell and intercell strap integrity. The CELLTRON ADVANCED helps prioritize battery replacements for more cost-effective system management by providing advanced warning of potential battery failures. Ensure that your system will never experience down time without battery backup power with the CELLTRON ADVANCED for UPS, telecommunications and broadband applications.

  • High ampere-hour (up to 6000 AH) battery test capability
  • 16 internal memory registers capable of storing 480 consecutive test results and string statistics
  • Quick re-test function to correct erroneous entries
  • Tests 2-volt through 16-volt batteries on-line or off-line
  • Voltage measurement to 3 decimal places
  • 16 volt testing capability
  • Tests multiple intercell connectors and 8 posts
  • Enhanced backlit display and screen resolution
  • Voltage logging only option
  • No external power source needed
  • Portable IR wireless printing and data transfer to PC laptop
  • User definable battery reference number storage and fault threshold

For use in the following Application Markets:

  • Telecommunication battery testing and analyis
  • UPS battery testing and analysis
  • CATV/Broadband battery testing and analysis

NERC Compliance:

Midtronics battery testers and analyzers make compliance with the new NERC standard PRC-005-2 quick and easy.

Model Number: CTA-2000

Warranty: Midtronics standard one-year warranty

Applications:

  • Telecommunications (Central office and outside plant)
  • Power utility (generation, transmission and distribution) switching and station batteries
  • Uninterruptible Power Supply maintenance
  • Other professional stationary battery service

Conductance Range: 100-19,900 Mhos/Siemens

Battery Capacity Range: 10 Ah to 4000 Ah approx.

Power Requirements: One 9 volt high capacity/heavy duty lithium battery required (included), powered by battery under test for some test operations

Voltage Range: 1.0-15.0 Volts DC

Display: Enhanced backlit graphical LCD with resolution control for varying light environments

Operating Temperature: 0 to +40 degree C, 95% relative humidity, non-condensing

Interface Operations:

  • Dura probes
  • Dura clamps
  • Standard clamps
  • Mini-probes
  • End-of-Train device cable
  • Others, including customs available

Housing Material: Acid and impact resistant ABS plastic

Product Dimensions: L9″ X 4″ X 2.5″ (230 mm X 102 mm X 65 mm)

Product Weight: 1 lb / 427 grams

Over Voltage Protection: Fused protection to 60-volts DC

Test Data Storage: 16 strings of 480 tests

Temperature Compensation: Automatic adjustments on temp input

Calibration: Auto calibration prior to every test, no future calibration required

© GFS Power. Website by Mick's Design.