DC Power System 48V
COMMANDER
Incredible Functionality, Flexibility, and Scalability in a 5 RU, 1.0 to 14.0 Kw DC Power System
- 19″, 5U rack mount shelf with integrated power distribution
- 90-250 VAC input, Power Factor Corrected
- 7 power bays accept 1000 or 2000 watt modular rectifiers
- 259 amp, 14,000 watt total max. output capacity, (222 Amp, 2,000 Watt, N+1) @ – 54 VDC
- Output temperature compensated for precise battery charging
- 18 DC circuit breaker distribution capacity, with tripped breaker alarm, 63 amp max. circuit breaker rating
- Master disconnect breakers for four battery banks, with tripped breaker alarm
- Controller with digital display of system parameters with TCP/IP interface and SNMP monitoring/logging
- Alarm contacts monitor major system functions
- Low voltage disconnect built in
- Easily configures to meet site power requirements
System Power Configurations @ 48V* (220 VAC Input) | |||||||
Watts Per Rectifier | # of Rectifiers Installed | ||||||
1 | 2 | 3 | 4 | 5 | 6 | 7 | |
2000 | 37A (2000W) |
74A (4000W) |
111A (6000W) |
148A (8,000W) |
185A (10,000W) |
222A (12,000W) |
259A (14,000W) |
* @ 120 VAC:Derate 2kW rectifiers: 41%; 1Kw: rectifiers 33% |
AC Input:
- Nominal: 230V
- Voltage Range: 90-300V (derate @ 115 input)
- Wiring Options: Single 208-240VAC, 3 phase, 4 wire WYE (‘Y’) input or 3 x separate 208-240VAC, 2 wire inputs
- Frequency Range: 45-65 Hz
- Power Factor: >0.99
- Efficiency: >94% (from 30-95% output power)
DC Output:
- Voltage: -48 volt
- Output Ratings: Constant power output from 48V to 58V
- Nominal Voltage: 48V
- Rated Voltage: 58V
Power:
- Rated maximum System Output Power: 14,000W @ -48V
- Polarity: Positive Earth (or specify)
- Individual Rectifier Power:
(48 volt) | 2000 watt | |
Amperage @ 230 vac in | 37 | |
Amperage @ 115 vac in | 21 |
DC Distribution:
- Load: 18 breaker positon capacity, available amperages (specify) 6A, 10A, 15A, 20A, 30A and 63A tripped breaker alarm
- Battery: 4 x 100A battery circuit breakers.
- Breaker Fail Detection: Electronic fail detection on both load and battery breakers
- Low Voltage Battery Disconnect: 300A battery LVD installed standard, with disconnect alarm
Monitoring & Control:
Monitors all power system conditions including DC voltage, rectifier current, battery current, battery temperature, and distribution failure. Visual notification of alarm conditions by LED’s and a 4 line x 16 character alpha numeric display mounted on the front panel, with remote notification being enabled by relay contacts, RS232 or TCP/IP (using SNMP). It has a built-in web based configurator allowing setup of system parameters using a web browser and utilizes a USB communications port which allows for local monitoring of system operations as well as easy downloading of configuration files for multiple site installations.
Protection:
- Current Limit: Adjustable to 50-100% of maximum rated current.
- Over Temperature: Automatic current reduction, backup shutdown protection.
- Polarity Reversal: Output fuse with crowbar diode.
- Over Voltage: Adjustable limit.
- Input Voltage: Auto shutdown, auto restart when correct voltage restored.
- Input Inrush: <2x maximum input current.
- Input Fuses: In phase and neutral.
Technical Characteristics:
- Noise: Ripple <100Hz: <1mV rms unweighted
- Voice band 100Hz-5KHz: <1mV rms psophometric
- Wide band 5kHz-1MHz: <5mV rms unweighted
- Peak to Peak 0-20MHz: <100mV peak to peak
- Isolation: Input to Output: 4000V DC.
- Input to Chassis: 3500V DC (VDR to chassis removed)
- Output to Chassis: 2100V DC
- Regulation: Line = +/-0.1%, Load = +/-0.5% (no load to full load)
Mechanical:
- Shelf: Dimensions / 19″ W x 8.75″ H x 15.35″ D /
- Weight: 35.15 Lbs. (excluding rectifier modules)
- Rectifers: Dimensions / 4.25″ W x 2.75″ W x 11.1″ D /
- Weight: 3.15 Lbs
- Cooling: Forced cooled
Environmental:
- Ambient Temperature: Nominal: 25+/-5°C
- Range: -10°C to +70°C (maximum output power is derated above +50°C)
- Humidity: 5-95% RH (non-condensing)
- Altitude: <8,202 ft., De-rate maximum ambient temperature by 4°C per 3,280 ft. above sea level.
Compliances:
- Safety: EN60950
- Electrostatic Discharge: CISPR24
- Radiated Radio Freq: CISPR22
- AC Harmonics: EN61000-3-2
- AC Flicker & Fluctuation: EN61000-3-3
- Other: CE & RoHS compliant