DC Power Supplies – Linear Heavy Duty
Linear Heavy Duty Power Supplies – 12 VDC and 24 VDC
Ideal for rugged hostile environments
Heavy Duty Linear Power Supplies - super-rugged DC linear power supplies are ideal for powering 12 and 24 volt communication equipment in base stations, remote sites and portable communication applications where reliability is essential. The proven linear circuit design provides pure output and long life.
Heavy Duty Linear Power Supplies have been produced by Newmar for more than 25 years and are used in communication systems world wide where high reliability in hostile environments is essential.
- Excellent Regulation and Ripple Spec: Output voltage maintained within 1% under all line and load conditions within rating; Ripple is less than 40 mV P-P. (12 volt) or 70 mV P-P (24-volt)
- Input voltage 115 or 230 VAC selected by slide switch on the front panel.
- Polyurethane conformal coated PC board and corrosion resistant heavy duty aluminum case with integral shock mounts assures survival in hostile environments
- Heat generated by semi-conductors is extracted and dissipated by large heat sink fins that maximize air contact for cool operation and long life of components.
- Supply and Load Circuit Protection: over-voltage, current limit; (set @ 105% of intermittent rating), thermal overload and input / output fusing.
- Thermally activated cooling fan on “CD” units.
Model 12Volt Output | Nominal Input/VAC | Output Amperage Intermittent Continuous | Case Size Ref. | Weight Lbs. Kg. | ||
115-12-8 | 115 / 230 | 8 | 5 | P-2 | 10 | 4.5 |
115-12-20A | 115 / 230 | 20 | 8 | P-3 | 20 | 9.1 |
115-12-35CD | 115 / 230 | 35 | 35 | P-5 | 32 | 14.6 |
24 Volt Output | ||||||
115-24-10 | 115 / 230 | 10 | 4 | P-3 | 20 | 9.1 |
115-24-18CD | 115 / 230 | 18 | 18 | P-5 | 32 | 14.6 |
115-24-35CD | 115 / 230 | 35 | 35 | P-6 | 60 | 27.3 |
Inches |
Centimetres |
|||||
Case Size Ref. |
Height | Width | Depth | Height | Width | Depth |
P-2 | 6.0 | 4.6 | 8.5 | 15.2 | 11.7 | 21.6 |
P-3 | 5.7 | 4.8 | 16.3 | 14.5 | 12.2 | 41.4 |
P-5 | 6.5 | 9.5 | 14.0 | 16.5 | 24.1 | 35.6 |
P-6 | 6.5 | 13.0 | 18.75 | 16.5 | 33.0 | 47.6 |
Input Range
105-125 / 210-250 VAC (selectable), 50-60 Hz
Derate to 50% output below 110 and 220 VAC
Operating Temperature
Standard Units
0-50° C, Derate Linearly From 100% @ 40° C to 50% @ 50° C Thermal shutdown @ 85° C Case temperature C.D. Units
0-65° C, Derate Linearly From 100% @ 50° C to 50% @ 65° C Thermal Shutdown @ 85° C Case temperature
Duty Cycle
Intermittent: 20 minutes max on time, 20% duty
Continuous: 24 Hours / Day 100% Duty
Options
- Modify for use as a Battery Charger
- Output voltage adjust (see Output Voltage for range)
Output Voltage
- 12 V Models: 13.6 VDC (Internally adjustable 12.6 – 14.5 VDC), Ripple: 40 mV P-P (@ 110-125 / 220-250 VAC input)
- 24 V Models: 24.5 VDC (Internally adjustable 21.0 – 27.5 VDC), Ripple: 70 mV P-P ( @ 110-125 / 220-250 VAC input)
Regulation All Models: 1% Line and Load (@ 110-125 / 220-250 VAC input)
Option:
Extreme Vibration Mounting Kit - is available to protect Newmar power converters from the extreme stresses of shock and vibration when mounted on high–vibration vehicles. The kit replaces the standard vibration kit provided with the unit and fits into the unit’s mounting flange to act as a “super shock absorber” for electronics in high-vibe applications. It is available to fit all Newmar units from 2 to 70 lbs. Specify KIT–L for units which weigh 2–15 lbs. and Kit–H for units which weigh 16-70 lbs.