Celltron Advantage
Battery management and testing are critical for maintaining power integrity for telecom networks, data centers, utility transmission and distribution systems. The demand placed on these systems has increased dramatically in the past decade. Service providers, operations and maintenance teams need to gain an advantage over this mounting responsibility. The CELLTRON ADVANTAGE system provides a user-customizable, flexible, efficient and economical tool to take on this critical task.
Features complete software modularity/add-ons for what is needed to get the job done:
• Base unit provides battery Conductance (state of health assessment), voltage and integrated temperature measurement
• Custom modules available to meet battery program needs:
- Decision/Algorithm that provides estimated Ampere Hours by battery jar (Coming Soon)
- Guided test interface to simplify technician interaction
- Integrated site trending capability
- Multimeter functionality
- Discharge test manager: increase automation and accuracy of discharge test
- Generator starting battery test
All system levels offer these advantages:
• Highly efficient test process: 50% reduction in test time from other battery analyzers
• Less invasive testing approach reduces battery discharge, voltage measurement skew and allows for more tests on a single internal battery without recharge
• Full compatibility with Midtronics CELLTRAQ Battery Data Management System for simple and efficient data tracking, reporting and decision making; data transfer via USB
• Field software updates, including module add-ons
• Interchangeable test interfaces for technician ease of use and lower maintenance cost
• Integrated battery temperature measurement
• Integrated lighted test interfaces
• Test continuity/accuracy indication on test interfaces
• USB data connection and storage compatible
• On board battery pack to support test time of 6-8 hours
NERC Compliance:
Midtronics battery testers, analyzers and battery data management software make compliance with the new NERC standard PRC-005-2 quick and easy.
CAD-5000 (Base Kit)
CAD-5200 (Enhanced Kit)
CAD-5500 (Complete Kit)
Applications:
Tests individual Lead-Acid or Nickel-Cadmium cells or Monoblocs (up to 16Volts) in any common configuration, approximately 10-6000Ah.
Voltage:
0.8 – 20.0 Volts DC
Conductance:
100 – 19,990 Siemens
Test Data Storage:
14000 tests stored internally, unlimited with USB drive connected
Accuracy: +/- 2% across test range, Voltage and Conductance
Voltmeter Resolution:
5 mV
User Programmable Functions:
• Preset values for over 250 battery types
• Low voltage alarm setting
• Low conductance warning
• Low conductance failure
• Test mode (push button/auto start)
Calibration:
Auto-calibration prior to every test, no future calibration required Connectorized Test
Cable Options:
• Dual contact clamps
• Dual contact probes
• Custom cables by quotation
Power Requirements:
• 7.2V, 2500AH, NiMH
• Internal swappable battery & charger
Display:
LCD – FSTN 2.619 in x 1.309 in, 128 x 64 pixels, 40 degree viewing angle, contrast ratio 8, Green LED backlight
Keypad:
Alph-numeric, Stainless-steel dome, polycarbonate overlay, 1,000,000 actuations
Data Transfer:
• USB Flash Drive (Type A)
• USB PC Interface (Type B)
• Infra-red, half-duplex IRDA
• Protocol for printer
Environmental Operating Range:
0 to +40C, 95% relative humidity, non-condensing
Storage Temperature:
-20 to 82C
Over Voltage Protection:
• Auto-reset disconnect
• Reverse polarity protected
Housing Material:
Acid resistant ABS plastic santoprene overmold
Analyzer Dimensions:
• 11 in x 4 in x 3 in
• 280 mm x 105 mm x 80 mm
Case Dimensions:
• 19 in x 15.5 in x 7 in
• 485 mm x 395 mm x 180 mm
Analyzer Weight:
1Kg / 2.6 lb
Shipping Weight:
Approximately 5Kg/11 Lbs