GFS Power

FCA 2500R..AC/AC Frequency Converter

FCA2500R

FCA2500R series is a compact AC/AC frequency converter which uses established design techniques to ensure high reliability. Suitable for a wide range of applications.

FCA2500R features full electronic protection, high efficiency and low output noise. The built-in fan provides sufficient airflow for operation without de-rating up to 50ºC ambient temperature.

Extended operating temperature (-40 to +65ºC) is available. The converter can be loaded with a fluorescent lamp load up to the full specified output power.

Input Voltage: 115 or 230VAC, 48…410Hz +/-20% are standard; Other inputs available, please consult factory

Input Protection: Thermal fuse, Inrush current limiting, Reverse polarity protection

Isolation: 2250 VDC input to chassis / 2250 VDC input to output / 2250 VDC output to chassis

Output Voltage: 230VAC/10.8A continuous at 50, 60, or 400Hz with grounded neutral; Isolated floating output optional (Consult factory for other voltages and frequencies)

Wave Form: Sinusoidal

Total Harmonic Distortion: Less than 5% at full load

Efficiency: Min 78% at full load

Line Regulation: Maximum 0.5%

Load Regulation: Maximum ±2% from no load to full load

Output Protection: Current limiting with short circuit protection, thermal shutdown with automatic recovery in case of continuous overload or insufficient airflow

EMI: Meets EN 55022 Class B

Load Crest Factor: Maximum 3.0 at 90% load

Operating Temperature Range: 0°C to +50°C Extended range available (Consult factory)

Humidity: 5 - 95% non-condensing

Temperature Drift: 0.05% per °C over operating temperature range

Dimensions: 6U” X 19” x 15” enclosed case (H x W x L)

Connections: Input/Output: Terminal block

Weight: 48 pounds (21.8 Kg)

Safety: Designed to meet C22.2 No. 107.1 – 01, UL 458 and EN60950

Options: Output Fail Alarm (Form C); Remote Inhibit: By connecting DC voltage (as specified) to the inhibit terminals

 

© GFS Power. Website by Mick's Design.