Space Critical Power Solutions

  Rackmount DC - DC

 Home
Back
 
 
DC-DC CONVERTERS

RACKMOUNT SERIES

48VDC - 12VDC  30Amp  400Watt

48VDC - 24VDC  15Amp  400Watt

24VDC - 12VDC  30Amp  400Watt

POSITIVE   NEGATIVE  or  FLOATING GROUNDS

 

Communication sites require isolated DC Converters to provide excellent voltage regulation, low noise, and high efficiency voltage conversion. Reliability is vital under continuous duty operation and high ambient temperatures. All these aspects were incorporated in the design of our rack-mount DC Converters.

These units accept a wide input range at 24 or 48VDC nominal, positive or negative ground, and produce pure 12 or 24 volt power. The solid state circuitry is conservatively designed and semi-conductors are selected and tested to withstand 200% of normal operating power.

Output voltage is maintained within 1% for all line and load conditions and the output is well filtered, allowing use with sensitive transceivers and telecom equipment.

Features
• 48, 24 volt inputs; 12, 24 volt outputs; positive, negative or floating ground.
• Input/Output chassis isolation – 250VDC
• 400 watt output
• Rated for continuous duty at full load.
• Excellent regulation under all line/load conditions.
• Low ripple provides noise free output.
• High efficiency – 87% typical.
• Easily adapts to both 19" and 23" racks, centre mount (6" from front)
• Output volt and ammeter
• Output voltage adjustment on front panel
• Low profile – occupies two RU (one RU space above and below recommended for cooling)

Specifications
DC-DC Converters
Input
Voltage
(VDC)
Output
Adjustment
Range
Amperage
(continuous)
Weight
Voltage
(VDC)
Max
Amps
Lbs
Kg.
48-12-30RM
40-60
12
13.6
12.6-14.5
30
10
4.6
48-24-15RM
40-60
12
27.2
25.2-29.0
15
10
4.6
24-12-30RM
20–30
24
13.6
12.6-14.5
30
10
4.6

Performance
Regulation: 1% line/load
Ripple: +/– 1/2% peak-peak max.
Idle Current: 48V: <100 mA, 24V: 300 mA
Efficiency: 85% typical @ 50% load.
Operating Temperature: -20 to 50° C; Derate linearly from 100% @ 50° C to 50% @ 70° C
Isolation: 250 volts input-out put-chassis.

Rear View


Mechanical
• Powder coated aluminum front panel, vinyl coated aluminum case.
• Mounting brackets provided for 19" or 23" Rackmount, centre or front.
• Easy access terminal blocks on back of unit, with protective cover
• Front panel switch guard provided.
• Output voltage adjustment potentiometer recessed in front panel

Protection
• Input and Output circuit breaker.
• Current limited/short circuit proof.
• High/low input voltage shutdown
• Fail-safe components guard against output over-voltage condition.
• Automatic high temperature power reduction starting at 65° C heat sink temp.
• Automatic thermal shut down and recovery @ 80° C heat sink temp. (automatic reset @ 55° C heat sink temp.).
• Reverse polarity protection.

Options
• Operation as battery charger and /or parallel redundant operation. (Heat sink mounted oring diode installed in series with the output)
• Output Failure Alarm Contacts; Form C
• Current protection recommended on charging leads

Case Size R-1
 
Inches
Centimeters
H
W
D
H
W
D
3.5
19/23
14
8.9
48.3/58.4
35.6
 
 
Download PDF Data Sheet 

 

 

Home Back Contact Us Trading Terms Search

For pricing and availability please email : sales@gfspower.com.au

Should you have a requirement that cannot be met from the current Web site please email us @ sales@gfspower.com.au

Reseller inquiries are welcome, please email: raymond@gfspower.com.au

Last modified: 06-Jan-2014  