Space Critical Power Solutions

  Fuse Distribution

 Home
Back
 
 
48V DC    or    24V DC
 
FUSE DISTRIBUTION PANELS
 
DUAL 100Amp BUSES
 
MAX. 20 FUSE PANEL (10 PER BUS)
 
MAX. 40 FUSE PANEL (20 PER BUS)
 
CHOICE OF FUSES: 1A, 3A, 5A, 10A, 15Amp (OTHER RATINGS ON REQUEST)
 

These Fuse Panels are ideal for DC distribution to low power loads in 24 and 48 volt positive and negative ground network applications and provide enhanced system reliability via dual input buses which allow configuration with redundant power sources. Each input bus accommodates 10 or 20 GMT output fuses (depending on model) in ratings up to 15 amps. Form C alarm contacts provide remote monitoring of input power and blown fuse conditions. Front panel LEDs indicates normal operation, fuse failure mode, as well as a user configured external alarm signal. Their low profile 1.75” (1 RU) occupies minimal space and can be configured for 19 or 23 inch rack mounting.

Model

Nominal
Input/Output

Total Fuse
Capacity

Amps per Bus
(Dual Bus)

Total Current
Capacity

FDP-1010

+/- 24 or 48VDC

20

100

200A

FDP-2020

+/- 24 or 48VDC

40

100

200A

 
Features
GMT Fuse
• Form “C” alarm contacts
• Polarity insensitive panels work with positive and negative ground systems -/+ 24 or -/+ 48VDC
• 1RU (1.75”) in height will configure to 19” or 23” rack mounting


Operating Temperature
-20° to +60° C
-5° to + 140° F

Compliances
NEBS 3 certified

Mechanical
• Steel case painted flat black with white graphics
• Mounting ears provided for 19” and 23” rackmount, flush mount or 6” offset
• 1 RU (1.75”), can be zero clearance mounted directly adjacent to other equipment

 
Front Panel Details
LED status indicators:
    Normal Operation
    Fuse Alarm
    External alarm
Easy accessible fuse blocks
Spare fuse holder

Alarms
• Form C alarm contacts for each bus
• External ground input alarm (bay or rack alarms)

Specifications
 
Nominal Input/Output: +/- 24 or +/- 48VDC
Total Fuse Capacity:
    FDP 1010 - 10 GMT fuses per bus
    FDP 2020 - 20 GMT fuses per bus
Total Current Capacity:
    FDP 1010: 200 amps (dual 100 amp bus)
    FDP 2020: 200 amps (dual 100 amp bus)
Fuse Holder & Fuse Rating:
15 amps max.

GMT Fuses: Available amperages: 1, 3, 5, 10, 15 Other ratings available upon request
Note: Fuses sold separately

Rear Panel Details
Input Terminal Block: Two 1⁄4” studs on 5/8” centres
Output and Alarm Terminal Blocks:
    FDP 1010: Barrier Terminal Block; #22 to #10 AWG wire for fork or ring #6 screw
    FDP 2020: Elevator clamp style terminal block; #26 to #12 AWG wire.
Cable Management Bar
Clear Lexan cover protects wiring connections

Case Size

Inches
Centimeters

(H) 1.75 x (W) 17 x (D) 11.5

(H) 4.5 x (W) 43.2 x (D) 29.2

Weight: 8 pounds (3.6kg)

Download PDF Data Sheet 

Download PDF Installation / Operation Manual: - Model FDP1010 
 
Download PDF Installation / Operation Manual: - Model FDP2020 
 

 

Home Back Contact Us Trading Terms Search

For pricing and availability please email : sales@gfspower.com.au

Should you have a requirement that cannot be met from the current Web site please email us @ sales@gfspower.com.au

Reseller inquiries are welcome, please email: raymond@gfspower.com.au

Last modified: 06-Jan-2014  

Webmaster: GFS Power