Centurion II SERIES
Incredible Functionality,
Flexibility, and Scalability in a 2 RU, 1.0 to 6.0 Kw DC Power System
Features:
-
19", 2U rackmount
shelf with integrated power distribution
-
90-250 VAC input,
Power Factor Corrected
-
3 power bays accept
1000 or 2000 watt modular rectifiers
-
111 amp, 6000 watt
total max. output capacity, (74 Amp, 4000 Watt, N+1) @ - 48 VDC
-
Output temperature
compensated for precise battery charging
-
16 DC circuit breaker
distribution capacity, with tripped breaker alarm
-
Master disconnect
breakers for two battery banks, with tripped breaker alarm
-
Controller with
digital display of system parameters with TCP/IP interface and SNMP
monitoring/logging (also available with MODBUS/TCP)
-
Alarm contacts
monitor major system functions
-
Low voltage
disconnect built in
-
Easily configures to
meet site power requirements
Specifications:
System Power Configurations @ 48V*
|
Watts Per
Rectifier
|
# of Rectifiers
Installed
|
1
|
2
|
3
|
2000
|
37A (2000W)
|
74A (4000W)
|
111A (6000W)
|
1000
|
18A (1000W)
|
36A (2000W)
|
54A (3000W)
|
System Power Configurations @ 24V*
|
Watts Per
Rectifier
|
# of Rectifiers
Installed
|
1
|
2
|
3
|
2000
|
37A (1000W)
|
74A (2000W)
|
111A (3000W)
|
* @ 230 VAC
input, 2Kw: derate 41% @ 110 VAC input; 1Kw: derate 33% @ 110 VAC input
AC
Input
Nominal: 230V
Voltage Range: 90-300V (derate @ 115 input)
Frequency Range: 45-65 Hz
Power Factor: >0.99
Efficiency: >94% (from 30-95% output power)
DC
Output
Voltage
|
-48 volt
|
+24 volt
|
Output
Ratings:
|
Constant
power output
from 48V to 58V
|
Constant
power output from
24V to 29V
|
Nominal
Voltage:
|
48V
|
24V
|
Rated
Voltage:
|
58V
|
29V
|
Power:
Rated maximum System Output Power: 6000W @ -48V,
3000 watts @ 24 volts
Polarity: Positive earth. 48 volt, negative earth 24 volt
Individual
Rectifier Power: (24 and 48 volt)
|
1000 watt
|
2000 watt*****
|
Amperage @ 230 vac in
|
18
|
37
|
Amperage @ 115 vac in |
12
|
21
|
*****Model C2R-2000 is rated for 1000 watts or 37 amps at 24 volts
|
DC
Distribution:
Load: 16 breaker position
capacity, available amperages (specify) 6A, 10A, 20A, 30 amp, with tripped
breaker alarm
Battery: 2 x 100A battery circuit breakers.
Breaker Fail Detection: Electronic fail detection on both load and
battery. Breakers
Low Voltage Battery Disconnect: 125A battery LVD installed standard,
with disconnect alarm
Monitoring &
Control:
Monitors all power system conditions including DC voltage, rectifier
current, battery current, battery temperature, and distribution failure.
Visual notification of alarm conditions by LED's and a 4 line x 16 character
alpha numeric display mounted on the front panel, with remote notification
being enabled by relay contacts, RS232 or TCP/IP (using SNMP). It has a
built-in web based configurator allowing setup of
system parameters using a web browser and utilizes a USB communications port
which allows for local monitoring of
system operations as well as easy downloading of configuration files for
multiple site installations.
General System
Protection:
Current Limit: Adjustable to 50-100% of maximum
rated current.
Over Temperature: Automatic current reduction, backup shutdown
protection.
Polarity Reversal: Output fuse with crowbar diode.
Over Voltage: Adjustable limit.
Input Voltage: Auto shutdown, auto restart when correct voltage
restored.
Input Inrush: <2x maximum input current.
Input Fuses: In phase and neutral.
Technical Characteristics:
Noise: Ripple <100Hz: <1mV rms unweighted
Voice band 100Hz-5KHz: <1mV rms psophometric
Wide band 5kHz-1MHz: <5mV rms unweighted
Peak to Peak 0-20MHz: <100mV peak to peak
Isolation: Input to Output: 4000V DC
Input to Chassis: 3500V DC (VDR to chassis removed)
Output to Chassis: 2100V DC
Regulation: Line = ±0.1%, Load = ±0.5% (no load to full load)
Mechanical:
Shelf: Dimensions 19" W x 3.5" H x 15.35" D (19" x
2U x 389.89mm)
Weight: 19.84 Lbs (9.01kg) excluding rectifier modules
Rectifiers: Dimensions 4.25" W x 2.75" W x 11.1" D (107.95mm x 69.85mm x
281.94mm)
Weight: 3.15 Lbs (1.43kg)
Cooling: Forced cooled
Environmental
Ambient Temperature:
Nominal: 25+/-5º C
Range: -10º C to +70º C (maximum output power is derated above +50º C)
Humidity: 5-95% RH (non-condensing)
Altitude: <8,202 ft., De-rate maximum ambient temperature by 4º C per
3,280 ft. above sea level.
Compliances:
Safety: EN60950
Electrostatic Discharge: CISPR24
Radiated Radio Freq: CISPR22
AC Harmonics: EN61000-3-2
AC Flicker & Fluctuation: EN61000-3-3
Other: CE & RoHS compliant
Download PDF Data Sheet
|