Power
Modules
These versatile Rectifier
Modules function as either power supplies or battery chargers for 12, 24 or
48 volt systems; positive, negative or floating ground. They may be employed
singly or in combination, enabling the installer to scale the system
anywhere from 500 to 10,000 watts per rack. Units may be paralleled for N +
1 redundancy and alarm contacts allow local or remote monitoring. An
optional DC quick connect wiring kit allows easy replacement of modules
without system shutdown.
Power Modules may be used
separately as a power source, or they may be integrated with the
Power Function Manager (see
RPS System to greatly expand the system capability with other functions
such as digital output monitoring, powering multiple loads via circuit
breaker distribution and low voltage battery disconnect).

Power Modules integrated in
complete system
Features
-
12, 24 or 48 volts
output; pos., neg. or floating ground
-
115 or 230 VAC, 50-60 Hz
input 560 & 1000 watt models
-
230 VAC only 2200 watt
model
-
560, 1000 or 2200 watts
per module (approx.)
-
Built-in oring diode for
parallel or N + 1 configuration
-
Power supply or battery
charger operation (DC UPS system)
-
Optional battery
charging circuit: three-step charging, gel/lead-acid switch, and
temperature compensation
-
Form C alarm contacts
-
19" or 23”, 2 RU, flush
or 6” forward rack-mount
Model
|
Input Amps
@ Full Load
115/230V
|
Output
|
Watts
|
Weight
|
VDC
V Out
|
VDC
V2
|
Amps
Cont.+
|
Lbs
|
Kg.
|
PM-12-40A
|
8.5/4.3
|
13.6
|
14.3
|
40
|
560
|
12.2
|
5.5
|
PM-12-80
|
16/8
|
13.6
|
—
|
80
|
1000
|
15.2
|
6.9
|
PM-24-20
|
8.5/4.3
|
27.2
|
27.9
|
20
|
560
|
12.2
|
5.5
|
PM-24-40
|
16/8
|
27.2
|
—
|
40
|
1000
|
15.2
|
6.9
|
PM-48-10
|
8.5/4.3
|
54.4
|
55.1
|
10
|
560
|
12.2
|
5.5
|
PM-48-20
|
16/8
|
54.4
|
—
|
20
|
1000
|
14.0
|
6.4
|
PM-48-50
|
*/22
|
54.4
|
—
|
50
|
2200
|
34
|
15
|
VDC (V out) Measured at output terminal with oring diode
* 230 VAC input only
VDC (V2) Measured at direct output terminal
+ For parallel configuration/load sharing derate output 10%
|
Performance Specifications
Input:
85 - 135/170-270 VAC (selectable), 47 - 63
Hz., 560 watt models
90 - 265 VAC, 1000 watt models
207 - 253 VAC, 2200 watt model
Power Factor:
0.7, 560W & 2200W models
0.98, 1000W models
Regulation:
± 1% at direct output (V2); ± 2% through "oring" diode (V out)
Ripple:
1% (Typical)
Efficiency: 80-85% @ full load
Front panel Output Voltage Adjustment Pot Range: ±10%
Altitude Range: Full output to 5,000 feet. Derate output
current 4% per 1,000 feet to 10,000 feet max.
Temperature Rating
560 watt models:
-40° C to +60° C; Derate linearly from 100% load @ 50° C to 75% @ 60° C
1000 watt models: -20° C to + 70° C; Derate linearly from
100% load @ 50° C to 50% @ 70° C
2200 watt model: 0 - 50° C
Mechanical/General
-
Powder coated aluminum
front panel and cover
-
Vinyl laminated base and
cover
-
19” Rackmount brackets
provided
-
Wallmount via optional
brackets
-
AC Input wiring:
560 watt units: IEC AC entry, 6’ IEC cord with NEMA 5-15 plug
provided
1000 watt units: IEC entry, 6’ IEC power cord with NEMA 20 plug provided
2200 watt unit: Hardwire junction box, no power cord provided
-
1/4” -20 Output stud
(560 watt models)
-
Output bus bar (1,000 &
2200 watt models) with 1/4” - 20 bolts
-
Output “OK” L.E.D.
-
Multi colour LED: Green
= Ok, Red = Fail (1000W models only)
-
Loss-of-output alarm
contacts- Form C, plus loss of AC alarm contacts
Form C (1000 & 2200 watt units only)
-
Front panel voltage test
points
Options
-
Three stage charger
function with gel/ lead-acid selector Model: CFB (560 & 1000 watts only)
-
Temperature compensation
(for battery charging). All models.
-
DC Quick Connect Wiring
Kit:
560 watt models: QCK-3 (for 2-3 unit PM system) & QCK-6
(for 4-6 unit PM system)
1000 watt models: QCK-3A (for 2-3 unit PM system) &
QCK-6A (for 4-6 unit PM system)
2200 watt model: CCK-4
-
“Universal” mounting
bracket; Model: UMB-PM (500 & 1KW models only)
-
Metering, alarms, LVD
and distribution breakers (PFM-400 or ULM-100 module options)
Protection
-
Output fuse for reverse
polarity
-
Current limit
-
Input circuit breaker
-
Automatic high temp.
output
power reduction (560W & 2200W models)
-
Forced air cooling with
filter provided (560W models only)
Design Standards
-
UL 1950 / EN 60950
(Safety)
-
EN 50082 (Immunity)
-
EN 55014 (Conducted)
Case Size – All Models
|
H
|
W*
|
D
|
|
Inches
|
3.5
|
17
|
20.5
|
Centimeters
|
13.5
|
43.2
|
52.1
|
*19”
mounting brackets provided
Download PDF Data Sheet
|