Space Critical Power Solutions

  Inverter 5KVA

 Home
Back
 

 

INVERTER - RACKMOUNT

5kVA

19 / 23 3U

Pure Sine Wave

INPUT:   12V, 24V, 48V, 110  or  220VDC     OUTPUT:  100  -  120VAC (Tune VR)

INPUT:   12V, 24V, 48V, 110  or  220VDC      OUTPUT:  100  -  120VAC (Tune VR)

Features

Digital display

Bypass function (STS)

Advanced microprocessor

Loading controlled cooling fan

Output frequency:   50 / 60Hz switch

RS-232 interface / remote controls port / Wire connection to PC

Protection:   Input undervoltage      Overload      Short circuit      Low battery alarm      Input overvoltage      Over temperature

 

Item

24VDC 5kVA
3U
100 - 120VAC
48VDC 5kVA
3U
100 - 120VAC
110VDC 5kVA
3U
100 - 120VAC
220VDC 5kVA
3U
100 - 120VAC
24VDC 5kVA
3U
100 - 120VAC
48VDC 5kVA
3U
100 - 120VAC
110VDC 5kVA
3U
100 - 120VAC
220VDC 5kVA
3U
100 - 120VAC

Continuous Output Power

5000W
Maximum Output Power 5200W(3minutes)

Surge Rating

10000W

Input Voltage

24V 48V 110V 220V 24V 48V 110V 220V

Input Voltage Range

20-32
VDC
42-62
VDC
90-140
VDC
180-275
VDC
20-32
VDC
42-62
VDC
90-140
VDC
180-275
VDC
DC Input over voltage alarm 31VDC 61VDC 135VDC 270VDC 31VDC 61VDC 135VDC 270VDC
DC Input over voltage shut-down 32VDC 62VDC 140VDC 275VDC 32VDC 62VDC 140VDC 275VDC
DC Input under voltage alarm 21VDC 43VDC 95VDC 185VDC 21VDC 43VDC 95VDC 185VDC
DC Input under voltage shut-down 20VDC 42VDC 90VDC 180VDC 20VDC 42VDC 90VDC 180VDC
No load current draw 1.64A 0.82A 0.42A 0.24A 1.3A 0.68A 0.35A 0.18A
Output Voltage Adjustment

100 - 120VAC (Tune VR)

200 - 240VAC (Tune VR)

Frequency

50/60Hz 0.05% (Switch Selectable)

Peak Output Current

91A

45A

Efficiency (full load)

85% 87% 90% 92% 90% 92% 94% 94%

Standby current draw

1.5W Power Saving Mode

Output Waveform

R Load Pure Sine Wave <3% THD

P.F.

1.0 1.0
DC Input over voltage shut-down 16.0VDC 32.0VDC 62.0VDC 140.0VDC 275.0VDC 16.0VDC 32.0VDC 62.0VDC 140.0VDC 275.0VDC
DC Input under voltage alarm 10.5VDC 21.0VDC 43.0VDC 95.0VDC 185.0VDC 10.5VDC 21.0VDC 43.0VDC 95.0VDC 185.0VDC
DC Input under voltage shut-down 10.0VDC 20.0VDC 42.0VDC 90.0VDC 180.0VDC 10.0VDC 20.0VDC 42.0VDC 90.0VDC 180.0VDC

Protection

Overload, Short Circuit, Reverse Polarity (Fuse), Input Overvoltage, Input Undervoltage, Over Temperature

Digital Display

OVP, UVP, OTP, OLP, VAC, AMP, WATT, VDC, TEMP, Hz

Safety

EN60950-1

EMC

FCC Class A

EN 55022:2006,(Class A)
EN 61000-3-2: 2006
EN 61000-3-3: 1995/A1: 2001+A2: 2005

Power Saving Recovery Time

8 seconds

Interface Control Port

RS-232C With Baud Rate 2400, 4800, 9600, 19200 (Switch Selectable)

Remote Control Unit

Optional (RF Remote Control or Wire Control)

AC Input

110VAC

220VAC

AC Frequency

(50Hz-60 Hz) +/- 3%

(50Hz-60 Hz) +/- 3%

Bypass

4-6ms

4-6ms

Operating Temperature Range

-20C to 50C

Storage Temperature Range

-30C to 70C

Dimensions

504(L) 425(W) 132(H) mm

Weight

19kgs

Note: The specifications are subject to change without notice.

 